Skip to content

Indoor Comfort Map - [source code]

Per-point thermal comfort from probed indoor CFD fields: PMV/PPD (EN ISO 7730), operative temperature, ISO 7730 draught rate (from k when probed, else Tu = 40 %), head-to-ankle temperature difference (ISO 7730 PD and ASHRAE 55 PPD), ADPI (ASHRAE 113, cooling) and the share of points meeting ISO 7730 categories A/B/C, EN 16798-1 I-IV and ASHRAE 55. Probe the same points for T, U, k (and T again at head and ankle height). Temperatures in kelvin — what OpenFOAM writes — are converted automatically. Not assessed: radiant asymmetry, floor temperature, and ASHRAE 55's SET method for points above 0.2 m/s (reported separately). Formulas pinned against pythermalcomfort (Tartarini & Schiavon 2020) and ISO 7730 Annex D.

Input

Name Nickname Description Type
Air Temperature Ta Air temperature at each occupant point, at body height (0.6 m seated / 1.1 m standing): the Probe's T (kelvin is converted) or °C. Generic Data
Air Speed V Mean air speed at the same points: the Probe's U vectors (their magnitude is used) or speeds in m/s. Generic Data
Turbulent Kinetic Energy k Probed k (m²/s²) at the same points, for the draught rate's turbulence intensity Tu = 100·√(2k/3)/v. Unwired: ISO 7730's default Tu = 40 %. Generic Data
Radiant Temperature Tr Mean radiant temperature (°C or K): one value for the room or one per point. Unwired: equal to the air temperature (walls at air temperature — say so in a report). Generic Data
Relative Humidity RH Relative humidity (%), one value or one per point. Number
Head Temperature Th Air temperature at head height (1.1 m seated / 1.7 m standing), one per point. With Ankle Temperature it drives the vertical-difference criterion; also used as the draught (neck) temperature. Generic Data
Ankle Temperature Tf Air temperature at ankle height (0.1 m), one per point. Generic Data
Metabolic Rate M Metabolic rate (met). Number
Clothing Clo Clothing insulation (clo). Number
Posture Pos Seated or standing: sets which heights the head/ankle probes represent and the ASHRAE 55 gradient span. Text
Control Temperature Tc ADPI control temperature (°C). Unwired: the mean of the air temperatures. Number

Output

Name Nickname Description Type
PMV Predicted Mean Vote per point (EN ISO 7730). Number
PPD Predicted Percentage Dissatisfied per point (%). Number
Operative Temperature To Operative temperature per point (°C, ISO 7726). Number
Draught Rate DR ISO 7730 draught rate per point (%). Number
Vertical PD PD ISO 7730 percentage dissatisfied from the head-ankle difference per point (%); empty without head/ankle input. Number
Effective Draft Temperature EDT ASHRAE 113 effective draft temperature per point (K). Number
ISO 7730 Category ISO Best ISO 7730 category met per point (A/B/C/Outside). Text
EN 16798-1 Category EN Best EN 16798-1 category met per point (I-IV/Outside). Text
ASHRAE 55 A55 Per point: Compliant, NotCompliant, or ElevatedAirSpeed (above 0.2 m/s — the SET method applies, not assessed here). Text
Summary Sum Occupied-zone statistics. Text
Comfort Map Map The whole map, for the Ventilation & Comfort Report. Generic Data