Per-point thermal comfort from probed indoor CFD fields: PMV/PPD (EN ISO 7730), operative temperature, ISO 7730 draught rate (from k when probed, else Tu = 40 %), head-to-ankle temperature difference (ISO 7730 PD and ASHRAE 55 PPD), ADPI (ASHRAE 113, cooling) and the share of points meeting ISO 7730 categories A/B/C, EN 16798-1 I-IV and ASHRAE 55. Probe the same points for T, U, k (and T again at head and ankle height). Temperatures in kelvin — what OpenFOAM writes — are converted automatically. Not assessed: radiant asymmetry, floor temperature, and ASHRAE 55's SET method for points above 0.2 m/s (reported separately). Formulas pinned against pythermalcomfort (Tartarini & Schiavon 2020) and ISO 7730 Annex D.
Input
Name
Nickname
Description
Type
Air Temperature
Ta
Air temperature at each occupant point, at body height (0.6 m seated / 1.1 m standing): the Probe's T (kelvin is converted) or °C.
Generic Data
Air Speed
V
Mean air speed at the same points: the Probe's U vectors (their magnitude is used) or speeds in m/s.
Generic Data
Turbulent Kinetic Energy
k
Probed k (m²/s²) at the same points, for the draught rate's turbulence intensity Tu = 100·√(2k/3)/v. Unwired: ISO 7730's default Tu = 40 %.
Generic Data
Radiant Temperature
Tr
Mean radiant temperature (°C or K): one value for the room or one per point. Unwired: equal to the air temperature (walls at air temperature — say so in a report).
Generic Data
Relative Humidity
RH
Relative humidity (%), one value or one per point.
Number
Head Temperature
Th
Air temperature at head height (1.1 m seated / 1.7 m standing), one per point. With Ankle Temperature it drives the vertical-difference criterion; also used as the draught (neck) temperature.
Generic Data
Ankle Temperature
Tf
Air temperature at ankle height (0.1 m), one per point.
Generic Data
Metabolic Rate
M
Metabolic rate (met).
Number
Clothing
Clo
Clothing insulation (clo).
Number
Posture
Pos
Seated or standing: sets which heights the head/ankle probes represent and the ASHRAE 55 gradient span.
Text
Control Temperature
Tc
ADPI control temperature (°C). Unwired: the mean of the air temperatures.
Number
Output
Name
Nickname
Description
Type
PMV
Predicted Mean Vote per point (EN ISO 7730).
Number
PPD
Predicted Percentage Dissatisfied per point (%).
Number
Operative Temperature
To
Operative temperature per point (°C, ISO 7726).
Number
Draught Rate
DR
ISO 7730 draught rate per point (%).
Number
Vertical PD
PD
ISO 7730 percentage dissatisfied from the head-ankle difference per point (%); empty without head/ankle input.
Number
Effective Draft Temperature
EDT
ASHRAE 113 effective draft temperature per point (K).
Number
ISO 7730 Category
ISO
Best ISO 7730 category met per point (A/B/C/Outside).
Text
EN 16798-1 Category
EN
Best EN 16798-1 category met per point (I-IV/Outside).
Text
ASHRAE 55
A55
Per point: Compliant, NotCompliant, or ElevatedAirSpeed (above 0.2 m/s — the SET method applies, not assessed here).
Text
Summary
Sum
Occupied-zone statistics.
Text
Comfort Map
Map
The whole map, for the Ventilation & Comfort Report.